SM39PWB-CYCZ side mounted differential pressure sensor

homeproductOil and Gas IoT InstrumentationDifferential pressure transmitterSM39PWB-CYCZ side mounted differential pressure sensor

Differential pressure transmitter/SM39PWB-CYCZ side mounted differential pressure sensor

SM39PWB-CYCZ side mounted differential pressure sensor
Product Categories Differential pressure transmitter

SM39PWB-CY differential pressure transmitter is used to measure the level, density, pressure and flow of liquid, gas or steam, and then convert it into 4mA~20mADC HART current signal output. It can also communicate with HART handheld terminal for parameter setting and process monitoring.

Label:

SM39PWB-CY differential pressure transmitter is used to measure the level, density, pressure, and flow of liquid, gas or steam, and then convert it into 4mA~20mADC HART current signal output. It can also communicate with HART handheld terminal for parameter setting, process monitoring, etc.

Standard Specifications

(The range is adjusted based on the standard zero point, stainless steel 316L diaphragm, and the filling liquid is silicone oil)

  1. Performance Specifications

Reference accuracy of span adjustment (including linearity, hysteresis and repeatability from zero point):

± 0.075% If TD>10 (TD=maximum range/adjustment range), then: ±(0.0075×TD)%

The square root output accuracy is 1.5 times the linear reference accuracy above.

Ambient temperature influence

Range code-20℃~65℃ total impactRange codeTotal impact of -40℃~-20℃ and 65℃~85℃
A±(0.45×TD+0.25)%×SpanA±(0.45×TD+0.25)%×Span
B±(0.30×TD+0.20)%×SpanB±(0.30×TD+0.20)%×Span
C/D/F±(0.20×TD+0.10)%×SpanC/D/F±(0.20×TD+0.10)%×Span

Over range impact

±0.075%×Span

Static pressure effect

Range codeImpact
A±(0.5%Span)/4MPa
B±(0.3%Span)/16MPa
F/G/H/I/J±(0.1%Span)/16MPa

Overvoltage Effect

Range codeImpact
A±0.5%×Span/4MPa
B/C/D/E±0.2%×Span/16MPa
F/G/H/I/J±0.1%×Span/16MPa

Long-term stability

Range codeImpact
A±0.5%×Span/1Year
B±0.2%×Span/1Year
F/G/H/I/J±0.1%×Span/1Year

Power supply impact

±0.001% /10V (12~42V DC), can be ignored.

  1. Functional specifications

Range and scope

RangekPa
 ARange0~1
scope-3000~3000
 BRange1~100
scope-16000~16000
 CRange100~500
scope-16000~16000
DRange500~3000
scope-16000~16000
 ERange3000~4000
scope-16000~16000
 FRange4000~10000
scope-16000~16000
 GRange1~100
scope16000~30000
 HRange100~500
scope16000~30000
 IRange500~3000
scope16000~30000
 JRange3000~4000
scope16000~30000

Range limit

It can be adjusted arbitrarily within the upper and lower limits of the measuring range.

It is recommended to select a range code with the lowest possible turndown ratio to optimize performance characteristics. Zero setting

The zero point and span can be adjusted to any value within the measuring range in the table, as long as: the calibration span ≥ the minimum span

Installation location affects

The change of the installation position parallel to the diaphragm surface will not cause zero drift. If the installation position changes more than 90° from the diaphragm surface, a zero position effect within the range of <0.4kPa will occur, which can be corrected by adjusting the zero. No range effect.

Output

Two-wire system, 4mA~20mADC, optional HART output digital communication, optional linear or square root output. Output signal limit: Imin=3.9mA, Imax=20.5mA

Response time

The amplifier component damping constant is 0.1s; the sensor time constant is 0.1s to 1.6s, depending on the range and range ratio. The additional adjustable time constant is: 0.1s to 60s. The impact on non-linear outputs (such as square root function) depends on this function and can be calculated accordingly.

Warm-up time

<15s

Ambient temperature

-40℃~85℃

With LCD display and fluoro rubber seal -20℃~65℃ Storage temperature/transportation temperature

-50℃~85℃; with LCD display: -40℃~85℃ Work Pressure

Rated working pressure is divided into three levels: 16MPa, 25MPa, 40MPaStatic pressure limit

From 3.5kPa absolute pressure to rated pressure, the protection pressure can be greater than 1.5 times the rated pressure and applied to both sides of the transmitter at the same time.One-way overload limit:

One-way overload up to rated pressureElectromagnetic compatibility (EMC)

See the Electromagnetic Compatibility Appendix on the next page

  1. Install

Power supply and load conditions

The power supply voltage is 24V, R≤(Us-12V)/Imax kΩ, where Imax=23 mA

Maximum power supply voltage: 42VDC

Minimum power supply voltage: 12VDC, 15VDC (backlit LCD display) Digital communication load range: 250Ω~600Ω

Electrical Connections

M20×1.5 cable gland, terminal block is suitable for wires of 0.5mm2~2.5mm2.Process connection

Both ends of the process connection flange have NPT 1/4 and UNF 7/16" internal threads.

  1. Physical specifications

Material

Measuring membrane box: stainless steel 316L

Diaphragm: Stainless steel 316L, Hastelloy C Process flange: Stainless steel 304

Nuts and bolts: Stainless steel (A4) Filling fluid: Silicone oil

Sealing ring: Nitrile rubber (NBR), fluororubber (FKM), polytetrafluoroethylene (PTFE) Transmitter housing: Aluminum alloy, with epoxy resin sprayed on the surface

Shell seal: Nitrile rubber (NBR) Nameplate: Stainless steel 304

weight: 3.3kg (without: LCD display, mounting bracket, process connection)

Enclosure protection gradeIP67

Electromagnetic compatibility table

Serial numberTest itemsBasic StandardsTest conditionsPerformance level
1Radiated interference (housing)GB/T 9254-2008 Table 530MHz~1000MHzqualified
 2Conducted interference (DC power port) GB/T 9254-2008 Table 1 0.15MHz~30MHz qualified
 3 Electrostatic Discharge (ESD) Immunity GB/T 17626.2-20064kV (contact) 8kV (air) B
 4 Radio frequency electromagnetic field immunity GB/T 17626.3-200610V/m(80MHz~1GHz) A
5Power frequency magnetic field immunityGB/T 17626.8-200630A/mA
6Electrical fast transient burst immunityGB/T 17626.4-20082kV(5/50ns,5kHz)B

Note 1: A performance level description: When tested, performance is normal within the technical specification limits.

Note 2: Description of performance level B: During the test, the function or performance is temporarily reduced or lost, but it can recover by itself, and the actual operating status, storage and data are not changed.

Dimensions

Unit is mm